Load inquiry (railway)

안녕하세요. 구조계산에서 4) 활하중에서 ③측벽에 작용하는 열차하중에서 토압계수를 0.5로 계산되어있는데요, 철도설계기준(노반편) 113 page 보시면 "구교 측면의 측압은 0.4의 가상토압계수를 적용할 수 있다." 라고 나와있습니다. 확인 부탁드립니다... ^^

Answer

안녕하세요. 한길아이티입니다. 철도설계기준(노반편) P167 를 보시면 "정지토압은 지하 박스 구조물 등과 같이 정지토압을 적용하는 것이 타당할 경우에 적용한다." 라는 규준에 의거하여 정지토압을 작용시켰습니다. 또한 통상적으로 흙의 내부마찰각을 35도 이상으로 적용시키지 않으므로 정지토압은 0.4보단 크게 작용하여 보다 불리하게 구조물을 해석하고자 정지토압을 적용하였습니다. 감사합니다.

More in this list

StatusProductNo.TitleViewsDate
AnsweredACulvert#268543Pile calculation report3292026-09-28
AnsweredACulvert#268536Setting section changes in culvert1742026-09-28
AnsweredACulvert#268524Design check not performed at wall center2172026-09-27
AnsweredACulvert#268523Applying moving vehicle loads2392026-09-27
AnsweredACulvert#268522Question about pile layout2632026-09-23
AnsweredACulvert#268521Question about features1302026-09-23
AnsweredACulvert#268510Question about joint check in Excel report output1852026-09-22
AnsweredACulvert#268499Error in STM analysis of corner region1442026-09-22
AnsweredACulvert#268471Launching the culvert program592026-09-18
AnsweredACulvert#268442All lines are displayed as dashed lines, what should I do?1402026-09-17
AnsweredACulvert#268429Question about U-type underpass1262026-09-17
AnsweredACulvert#268424Load position when applying railway loads to an underpass2372026-09-17
AnsweredACulvert#268417Changing girder dimensions1522026-09-17
AnsweredACulvert#268396Incorrect section check location for horizontal rebar1842026-09-16
AnsweredACulvert#268376Question about segment settings for U-type retaining wall1942026-09-15
AnsweredACulvert#268343Question about culvert drawing output1292026-09-15
AnsweredACulvert#268337Inquiry about checking retaining-wall-type wing walls3062026-09-14
AnsweredACulvert#268330About drawing output1542026-09-14
AnsweredACulvert#268318Some blocks not displayed1412026-09-14
AnsweredACulvert#268317Tank load for surcharge and moving loads3422026-09-14
Sign in to ask